13.5 Setting up the Controller Protective Box
Placing the controller protective box
(1) Place the controller protective box on a flat, level plane.
(2) Do not place anything within 150 mm from the heat exchanger of the controller
protective box.
Preparing a power supply
Make a single-phase 200 VAC power supply (86W for the FB-9, 35W for the FB-10)
ready for use.
Connect the power supply to the fan motor drive terminal.
Recommended cable: 1.25 mm
2
x 3-core (outside diameter: 11 to 13 mm)
Note 1: Make the controller protective box share the same circuit breaker of
the power supply (200 VAC) with the robot controller.
Note 2: Ground the controller protective box to prevent an electric shock.
Setting the robot controller into the protective box
(1) Remove the top cover from the controller protective box.
(2) For the VM-D controller protective box (FB-9), remove the wing bolt and take off
the partition plate (A).
(3) Put the robot controller into the protective box so that its rubber feet will be fitted
into the controller fixtures of the protective box.
(4) For the VM-D controller protective box (FB-9), secure the partition plate (A) with
the wing bolt.
(5) Route the necessary cables through the ducts and connect them. As shown
below, tie up each duct with an attached binding band.
Note: Tie up the opening of each duct not in use with an attached binding
band to prevent entry of dust, water, etc. into the controller protective
box.
Binding band
Binding band
Box
Box
Note: Tying up duct(s) not in use